Four Key Issues That Cannot Be Ignored In The Practical Application Of Fireproof Glass

Details

1. No distinction between fireproof glass and fireproof glass partition

Some buildings require both fireproof separation and aesthetic transparency during design, so fireproof glass partitions are used as fireproof separation measures, such as boutique partitions in performance-based commercial pedestrian streets, glass firewalls in large commercial spaces, and viewing windows in viewing shafts. However, designers often mark them as fireproof glass rather than fireproof glass partitions on the drawings. Fireproof glass partitions are composed of fireproof components such as fireproof glass, frames, sealing materials, and pads, and are a complete system. Fireproof glass is only a component of fireproof glass partitions. It must be installed in combination with inlaid frames and fireproof sealing materials to form fireproof glass partitions and meet the corresponding fire resistance limit standards of the specifications.

2. Issues that should be noted when adding sprinkler protection to fireproof glass

There are many problems in design and construction. For example, some shops on both sides of the commercial pedestrian street directly make decoration shapes on the fireproof glass, which affects the effect of sprinkler water distribution; some install sprinklers under the decorated brand door heads, which affects the heat collection of sprinklers; some door heads are installed between fireproof glass and sprinklers, causing obstruction; some construction units did not set up the pipes of the sprinkler protection system separately, and shared the same pipes with other sprinklers, resulting in the amount of sprinkler water and duration not meeting the design requirements; some construction units used the wrong type of sprinkler. In short, during construction, it should be ensured that the sprinklers can effectively protect the fireproof glass used for separation in a timely manner, which should be noted.

3. Misunderstandings in the design and construction of fireproof glass partitions
At present, many design units do not design engineering practices, and construction units have misunderstandings about the inspection report of fireproof glass. They think that as long as the selected fireproof glass has an inspection report, it will be fine. They ignore that the fireproof test is not just a few pages of test reports, but a set of systematic descriptions of the detailed size, material use, and fireproof performance of the fireproof system. Complete information. The types, thickness, shape, size, assembly details, node diagrams, and even the size and position of the fixing screws of the various frame materials and accessories used in the system during the test are described in detail. The fire resistance performance stipulates that the fire-resistant size of the fireproof glass sample should be selected from the actual large size for testing, and should not be less than 1200mm×700mm.
4. Problems in fire supervision
Some supervisors mistakenly believe that doors made of fireproof glass are fireproof doors, partitions made of fireproof glass are fireproof glass partitions, and windows made of fireproof glass are fireproof windows. It should be clearly understood that fireproof glass, fireproof glass partitions, fireproof doors, and fireproof windows are completely different fire protection products, and the corresponding inspection reports should be checked. Fireproof doors should also have type inspection reports.